; AI CH ALARM & SHUTDOWN TRIP CLASS *******
; 0 Off (dflt)
; 1 Class A Over
; 2 Class B Over
; 3 Class C Over
; 4 Class A Under
; 5 Class B Under
; 6 Class C Under
63000.1=0 ; AI Ch #01 ALARM TRIP
63000.25=0 ; AI Ch #01 SHUTDOWN TRIP
; AI CH ALARM & SHUTDOWN TRIP TH **********
; TRIP threshold; TRIP value required to
; fault channel (in channel units).
63001.1=0 ; AI Ch #01 ALARM TRIP
63001.25=0 ; AI Ch #01 SHUTDOWN TRIP
; AI CH ALARM & SHUTDOWN TRIP HYS *********
; TRIP hysteresis; difference between fault
; threshold of TRIPPED channel and clear-
; fault threshold (in channel units).
63002.1=0 ; AI Ch #01 ALARM TRIP
63002.25=0 ; AI Ch #01 SHUTDOWN TRIP
; AI CH ALARM & SHUTDOWN TRIP DLY TIME ****
; TRIP dly time between actual TRIP channel
; threshold exceeded and channel fault
; (in secs).
63003.1=0 ; AI Ch #01 ALARM TRIP
63003.25=0 ; AI Ch #01 SHUTDOWN TRIP
; AI CH SHUTDOWN DISCRETE OUTPUT ACTION ***
; Select SHUTDOWN Discrete Output non-fault
; state. (Note: Some SCANNERs force Discrete
; Output action to Normally Energized.)
;
; 0 Normally Energized (dflt)
; 1 Normally Deenergized
130.1=0
;